Our projects vary from component deliveries to total turnkey solutions including UPS, power distribution, low– and high voltage cabling, copper and fiber patching solutions, racks, cooling, management, modular fire suppressive rooms, Inergen or HI–FOG fire suppression, diesel generator and anything else needed to complete the Network Critical Pysical Infrastructure build in the data center.

It is mandatory for us at all times to take any neccessary environmental issues seriously, advising on the most efficient solutions using as little power as possible, giving the lowest cost possible within the customers budget and possible restrictions from the physical building and local restrictions.

At the moment the most efficient way of treating the exhaust heat from servers, storage, backup and networking equipment is handling the heat with InRow chillers closest to the heat source. We enclose the hot aisle with a plexiglass roof and a door at each end of the rack row.

The InRow chillers with variabel automatic speed fans keep the cold aisles at a level 22 degrees celsius, and as high as possible heat in the warm aisle, to use as little chilled waters as possible in combination with as little power as possible.

An example, the 30cm wide chilled water based rack with 8 fans, cooling down each 42U rack in the whole height, draws appr 0,84 liters pr second og chilled water and only max 1340W powers, delivering 18kW cooling in an open solution and nearly 30kW en enclosed cube solution.